Most Indian offices spend more on the conference room per square foot than on any other space, and most of them still get it wrong. The table is beautiful, the chairs are leather, the logo glows on the wall — and the first video call reveals that remote participants cannot understand anyone at the far end, the people near the window are silhouettes, the screen is too small to read a spreadsheet, and the sales team next door can hear every word of the board meeting through the glass. None of these problems is about taste. They are about sound, light and signal, and they are decided in the design drawings long before the furniture arrives.

Since the shift to hybrid work, the conference room has also changed its job. It is no longer just a room where people meet each other; it is a studio from which a meeting is broadcast to people elsewhere. That raises the bar for acoustics, camera framing, face lighting and network reliability, and it means that a room designed purely to look impressive can fail at its main task. In Indian cities, glass-fronted meeting rooms built off open-plan floors, hard vitrified floors and gypsum ceilings make the acoustic problem worse, and hot, glaring afternoons make the lighting problem harder.

This guide follows a conference room from its size and layout through acoustics, lighting, display and camera, power and data, air-conditioning and finishes, with dimensioned drawings, a worked reverberation calculation and indicative October 2026 costs. It goes deeper than the office interior and small-office guides on this site, and keeps their numbers: 1200 × 600 mm desks, 1200 mm clearance around meeting tables, about 500 lux in meeting rooms, and office fit-out bands of ₹800–2,000 per sq ft.

From the boardroom table to the hybrid meeting room

The word boardroom comes from the older meaning of board — a table — and for centuries the meeting room was simply a room built around a large table, lit by windows and later by a chandelier or ceiling lights. Presentations arrived with the blackboard and the flip chart, then the overhead projector, then the data projector and pull-down screen in the late twentieth century. Each step brought a new design problem: projectors needed dark rooms and a clear throw; screens needed to be seen over the heads of people in front.

Video calling has a longer history than most people think — AT&T demonstrated its Picturephone at the 1964 New York World's Fair — but for decades it remained an expensive, specialised studio service. Cheap broadband, flat-panel displays and all-in-one video bars changed that in the 2010s, and the pandemic years turned video into the default. Today the conference room has to serve two audiences at once: the people at the table and the people on the screen. That is why acoustics, face lighting and camera position, once treated as specialist extras, now belong in the basic design brief.

Size and layout: start from the table

A conference room is planned from the inside out. Each seated person needs about 600 mm of table edge as a minimum and 750 mm for comfort with a laptop and papers. Behind each chair, about 1200 mm of clear floor lets a person pull back, stand up and let someone walk behind — the same 1200 mm clearance recommended in the office guides on this site. At the display end, the first seats should be far enough back that people do not crane their necks; leaving the head of the table nearest the screen unseated is common in rooms used for presentations and video calls. Table width of 1000–1200 mm gives space for laptops on both sides and a centre zone for power and microphones.

CapacityTypical table (mm)Typical room (mm)Area per personNotes
4 personsRound 1000–1200 or square 12003000 × 3000 to 3000 × 3600≈ 2.3–2.7 m²Huddle room; a 55–65 in display on the wall
6 persons2000 × 10003600 × 3000 to 4200 × 3600≈ 1.8–2.5 m²Common in small offices; see the 500 sq ft guide
8 persons2400 × 1000–12004800 × 3600≈ 2.2 m²As in the office interior guide
10 persons3000 × 12006000 × 4200≈ 2.5 m²The worked example in this article
12 persons3600 × 1200–14006600 × 4500≈ 2.5 m²Consider two displays or a larger screen
16–20 persons4800–6000 × 1400–1500, or U / boat shape8000–9000 × 5000–5500≈ 2.3–2.6 m²Boardroom; ceiling microphones and a lectern position
Training (classroom)Rows of 1200 × 600 tables, 2 seats eachSize by rows; 900–1000 between rows≈ 1.8–2.2 m²Projection or large display at the front
Fig. 1 — Conference room 6000 × 4200 mm, 10 seats (1 m = 70 px) 6000 18003000 table1200 150012001500 sight line ≈ 5100 to far seat display door 1000 Display check 86 in, 16:9 image ≈ 1904 wide × 1071 high General content: 6 × 1071 ≈ 6400 ≥ 5100 ✓ Detailed content: 4 × 1071 ≈ 4300 < 5100 → 98 in or two displays Seats 750 per seat along table 1500 behind chairs (≥ 1200 clear) Head seat by screen left empty for the camera view Area 25.2 m² ≈ 271 sq ft ≈ 2.5 m² per person. Floor box at the table centre feeds power, data and display inputs. Camera (blue) sits at the display, aimed down the table axis so every face is seen from the front.
Fig. 1 — A 10-seat conference room planned from the table, with display sizing (mm)

Fig. 1 shows the method on a 10-seat room. A 3000 × 1200 mm table seats four per side at 750 mm each plus one at the far end. With 1500 mm on each long side the room is 4200 mm wide, and with 1800 mm between the display wall and the table plus 1200 mm at the far end it is 6000 mm long — about 271 sq ft, or 2.5 m² per person. A room that is 600 mm narrower still works on paper, but people at the sides will be pinned against the wall every time someone walks behind them, and the door swing will clash with the end chair.

Display and camera: sizing what people see

The display is sized from the farthest viewer, not from the wall. A long-used rule of thumb in the AV industry relates the image height to the distance of the farthest viewer: for general content such as video calls and presentations with large text, the farthest viewer should be no more than about six times the image height away; for detailed content such as spreadsheets, drawings and small text, no more than about four times. The AVIXA DISCAS standard formalises this kind of calculation for different viewing tasks. For a 16:9 screen the image height is about 0.49 times the diagonal, which gives the figures below.

Display (16:9)Image width × height (mm)Farthest viewer, general (≈ 6 × height)Farthest viewer, detailed (≈ 4 × height)Suits
55 in≈ 1218 × 685≈ 4.1 m≈ 2.7 mHuddle rooms, 4 seats
65 in≈ 1439 × 810≈ 4.9 m≈ 3.2 m6 seats
75 in≈ 1660 × 934≈ 5.6 m≈ 3.7 m8 seats
86 in≈ 1904 × 1071≈ 6.4 m≈ 4.3 m10–12 seats
98 in≈ 2170 × 1221≈ 7.3 m≈ 4.9 m12–16 seats, detailed content
Two displays or projectionPer screen as aboveEach screen sized for the far seatContent on one, faces on the otherBoardrooms, training rooms

Height matters as much as size. The bottom of the image should clear the heads of seated people in front — commonly about 900–1200 mm above the floor, higher in deeper rooms — while the top should not force the nearest viewers to tilt their heads back. The camera belongs at the display, centred, just above or just below the screen, so that when participants look at the remote people on the screen they also appear to look at the camera. A camera on a side wall shows profiles and the backs of heads. Choose a camera or video bar whose field of view covers the whole table from its mounting position; wide-angle video bars suit small rooms, while longer rooms may need a camera with optical zoom or automatic framing.

Acoustics: the problem nobody sees

Acoustics fail in conference rooms in three distinct ways, and each has a different cure. The first is reverberation: sound bouncing around a room of hard surfaces — glass, gypsum, vitrified tile, a polished table — so that speech blurs, especially for microphones, which cannot ignore echo the way human ears partly can. The second is background noise: air-conditioning, traffic and adjacent spaces masking speech. The third is speech privacy: conversations inside leaking out, or noise from outside leaking in, through partitions, doors, ceiling voids and ducts. Absorption cures the first; quiet services cure the second; mass, airtightness and continuity cure the third. Adding fabric panels does almost nothing for privacy, and a heavy partition does nothing for echo.

Acoustic targetTypical design aim (indicative)What controls itCommon Indian failure
Reverberation time (RT60, mid frequencies)≈ 0.4–0.6 s; towards 0.4 s or lower for video roomsAbsorptive ceiling, carpet, wall panelsGypsum ceiling, vitrified floor and glass: often above 1 s
Background noise from services≈ NC 25–30Low-velocity air, lined ducts, quiet indoor unitsCassette AC blowing directly above the table
Partition, normal privacyRw ≈ 40–45Insulated stud wall to slab, sealedPartition stops at the false ceiling
Partition, confidentialRw ≈ 50 or moreDouble-layer boards, insulation, double glazingSingle glass front and a hollow door
DoorSolid core with perimeter and drop sealsSeals matter as much as the leafUndercut door with a 10–15 mm gap
Duct crosstalkNo direct duct path between roomsLined bends or crosstalk silencersOne duct serving two rooms side by side

Rw, the weighted sound reduction index, describes how much a partition reduces airborne sound in laboratory tests; the US STC rating is similar in scale. Real rooms rarely achieve the laboratory value, because sound finds the weakest path — a gap at the head, a back-to-back socket, a door, a shared ceiling void. As a broad guide from published manufacturer data, a single 12 mm toughened glass panel sits in the low-to-mid thirties; an acoustic laminated glass of similar thickness a few points higher; a double-glazed partition with a wide cavity in the mid-forties and above; a single-layer gypsum stud wall without insulation in the mid-to-high thirties; and a double-layer gypsum wall with mineral wool in the cavity around fifty. Always use the manufacturer's tested value for the exact system being built.

Fig. 2 — Partition between a conference room and the open office A — Stops at false ceiling (leaks) B — Built to slab, sealed (works) sound path over the wall conferenceopen office void 300–600 2700 Lab Rw of the wall is bypassed — the ceiling tiles become the partition lined duct silencer mineral wool in cavity, double board each side acoustic sealant at head, base and around sockets no back-to-back boxes Continuous from floor slab to roof slab; door solid-core with seals; glass double-glazed A wall is only as good as its weakest path: gaps at the head, ducts, sockets and doors. Detail all of them, not just the wall.
Fig. 2 — Why partitions leak: stopping at the ceiling versus building to the slab (section, mm)

Reverberation: a worked example

Reverberation time can be estimated with Sabine's formula: RT60 ≈ 0.161 × V ÷ A, where V is the room volume in cubic metres and A is the total absorption — each surface area multiplied by its absorption coefficient, summed. For the 6000 × 4200 mm room in Fig. 1 with a 2700 mm ceiling, V is about 68 m³. Finished in the typical way — vitrified floor, plain gypsum ceiling, painted walls and one glass wall — the absorption with ten people and their chairs comes to roughly 9 m² units, giving an RT60 of about 1.2 seconds: lively enough that a video call sounds as if it comes from a bathroom. Change the floor to carpet tiles, put an acoustic mineral-fibre ceiling over most of the room and add about 8 m² of fabric-wrapped panels on the rear and solid side walls, and the absorption rises to roughly 31 m² units, bringing RT60 down to about 0.35 seconds. The absorption coefficients used are indicative mid-frequency values; for a real project, use the manufacturer's tested data.

Fig. 3 — Treating the 10-seat room (plan, 1 m = 50 px) 60004200 display fabric panels: solid wall + rear wall glass front (no panels) acoustic ceiling zone (dots) V = 6.0 × 4.2 × 2.7 ≈ 68 m³ Before (typical finish) tile floor 25.2 × 0.02 ≈ 0.5 gypsum ceiling 25.2 × 0.05 ≈ 1.3 walls and glass 55 × 0.04 ≈ 2.2 10 people + chairs ≈ 5.0 A ≈ 9 → RT60 ≈ 0.161 × 68 ÷ 9 ≈ 1.2 s After (treated) carpet tiles 25.2 × 0.30 ≈ 7.6 mineral-fibre 18 × 0.55 ≈ 9.9 gypsum border 7.2 × 0.05 ≈ 0.4 fabric panels 8 × 0.80 ≈ 6.4 other walls 47 × 0.04 ≈ 1.9 10 people + chairs ≈ 5.0 A ≈ 31 → RT60 ≈ 0.161 × 68 ÷ 31 ≈ 0.35 s Coefficients are indicative mid-frequency (500–1000 Hz) values; use tested data for real products. Put panels on surfaces facing each other (rear wall, solid side wall) to stop flutter echo between parallel walls. Wall panels work best between about 600 and 2100 mm above the floor — the height of seated and standing mouths. Absorption fixes echo, not privacy: the partition and its seals (Fig. 2) still decide what leaks out.
Fig. 3 — Where absorption goes, and what it does to reverberation (worked example)
AbsorberIndicative absorption (NRC / mid-frequency α)Where it worksIndicative cost (Oct 2026)
Mineral-fibre ceiling tile, 600 × 600 grid≈ 0.5–0.7Main ceiling area over the table₹90–180 per sq ft installed — verify locally
Fabric-wrapped glass-wool or mineral-wool panel, 25–50 mm≈ 0.7–1.0Rear wall and solid side wall at seated height₹350–900 per sq ft
PET felt panel or baffle, 9–12 mm≈ 0.2–0.5 flat on wall; higher with an air gapDecorative walls, ceiling baffles₹150–400 per sq ft
Perforated or slotted wood / MDF panel with backing≈ 0.4–0.8, depends on open area and backingFeature walls where a wood look is wantedPriced as panelling plus backing — verify locally
Carpet tiles on hard floor≈ 0.2–0.4Whole floor; also kills footfall and chair noiseWithin the ₹80–200 per sq ft office flooring band
Heavy curtain, pleated, off the glass≈ 0.3–0.6Glass walls and windows; also controls glarePer running ft of track plus fabric — verify locally
Plain gypsum, glass, vitrified tile≈ 0.02–0.05Reflective — the surfaces that cause the problem—

Lighting for the table and for the camera

A conference room needs light for two audiences. People at the table need about 500 lux on the work plane, with low glare, for reading and writing — the level IS 3646 (Part 1) and the office guides on this site use for meeting rooms — and the ability to dim the area near the screen during presentations. People on the call need to see faces, which means vertical light falling on faces from the front, not hard light from directly overhead. Downlights directly above seated people cast shadows under the eyes, nose and chin that the camera exaggerates; a bright window behind participants turns them into silhouettes as the camera adjusts its exposure.

The fix is a combination: diffuse linear or panel lighting running along both sides of the table axis, so light reaches faces from slightly in front; wall washing on the wall behind the participants, so the background is neither dark nor glaring; dimmable control of the zone near the display; and blinds or curtains on any window that the camera looks towards or that faces the screen. Neutral white of around 3500–4000 K with a colour rendering index of at least 80 — 90 is better for video — and a unified glare rating of about 19 or lower keep the room comfortable and faces natural on screen. Scenes for meeting, presentation and video call, recalled from one keypad at the door, make the system usable.

Fig. 4 — Long section, 2700 mm ceiling (1 m = 70 px) camera 86 in display diffuse linear light, both sides of table axis seated eye ≈ 1200 blind Heights (mm) ceiling 2700 display top ≈ 2070 display bottom ≈ 1000 seated eye ≈ 1150–1250 table top 725–750 Light ≈ 500 lux on table soft light on faces 3500–4000 K, CRI ≥ 80 UGR ≈ 19 or lower dim zone at display 2700 Avoid downlights straight above heads (shadows under eyes) and bright glass behind participants (silhouettes). Keep the camera close to eye level so remote people see faces, not foreheads; dim the light that falls on the screen. Dimensioned bars at right (gold): ceiling, display bottom, seated eye and table heights from the floor.
Fig. 4 — Section along the room: display, camera, eye levels and face lighting (mm)
Lighting itemRecommendation (indicative)Why
Horizontal illuminance on table≈ 500 lux, dimmableReading and writing; IS 3646 (Part 1) meeting-room level
Light on faces (vertical)Soft, from the front, a substantial fraction of the table levelFaces read naturally on camera without shadows
Colour temperature≈ 3500–4000 K, one temperature throughoutNeutral skin tones; no mixed colours on video
Colour renderingCRI (Ra) ≥ 80; ≥ 90 preferred for video roomsAccurate skin and product colours
GlareUGR ≈ 19 or lower; no bare sources in viewComfort over long meetings; screens stay readable
Display zoneSeparately dimmed; no light falling on the screenKeeps contrast for presentations
WindowsBlinds or curtains; none directly behind participants on cameraPrevents silhouettes and screen glare
ControlsScene keypad at the door: meeting / presentation / videoMakes the system usable by everyone

Power, data and AV: plan the paths first

Most conference-room technology problems are cabling problems in disguise: a floor box that was never installed, a conduit too small to pull a second cable, a display with no network point, a microphone that needs power where there is none. The AV equipment itself changes every few years; the paths for cables last as long as the fit-out. The rule is to design the paths generously and early — before the floor screed, before the ceiling is closed and before the joinery is made — and to leave draw wires and spare capacity in every conduit.

Fig. 5 — Cable paths in a 10-seat room (schematic, not to scale) AV rack / credenzaswitch, codec or PC,amplifier, UPS outlet Floor box at tablepower, LAN, USB-C/HDMI Ceiling microphonesPoE via LAN cable Wall keypadlighting scenes, blinds Building network2 LAN + Wi-Fi AP Dedicated circuitAV on UPS-backed supply Displaypower + LAN + video Camera / video barUSB or LAN to codec Booking paneloutside door, PoE Floor box to rack: two conduits of about 50 mm with draw wires, gentle bends and pull boxes on long runs. Separate power and data. Leave a spare conduit to the display wall and one to the ceiling above the table for future microphones.
Fig. 5 — Conference room cabling: what connects to what (schematic)
Room sizeDisplayAudio and cameraConnectionIndicative AV cost (Oct 2026)
Huddle, 4 seats55–65 inAll-in-one video barWireless presentation or one USB-C cable₹1.5–4 lakh — verify locally
Medium, 6–8 seats65–75 inVideo bar, extension microphone if the table is longTable floor box, wireless presentation₹3–7 lakh
Large, 10–12 seats86–98 in, or two displaysCamera with zoom or auto-framing; ceiling or table microphones; ceiling speakersFloor box, rack, control keypad₹6–15 lakh
Boardroom, 16–20 seatsTwo large displays or projectionCeiling microphone arrays, multiple cameras, DSPFull rack, control system, room-booking₹15 lakh and above — specialist design

Prices for AV vary widely with brands, warranties and whether equipment is consumer or commercial grade; commercial displays rated for long daily use cost more than televisions but last longer under office hours. Whatever the budget, three things are worth insisting on: every device in the room on the network with remote monitoring where possible, a single simple way to start a call and share a screen, and a written as-built drawing of every cable and conduit for the next upgrade.

Air-conditioning and fresh air in a crowded room

Conference rooms are the densest rooms in an office. Ten people produce roughly a kilowatt of heat between them, plus the display, lighting and laptops, in about 25 m² — far more per square metre than an open office. Meetings also run long, and carbon dioxide from breathing builds quickly in a sealed room, which is a common reason why afternoon meetings feel drowsy. Design the room as a separate air-conditioning zone with its own control; supply fresh outdoor air in proportion to the number of seats, as NBC 2016 Part 8 and ASHRAE Standard 62.1 require for meeting spaces (ASHRAE's conference-room rate is about 2.5 litres per second per person plus 0.3 litres per second per square metre); and consider a CO₂ sensor that raises fresh air when the room fills.

Noise from air-conditioning is the most common acoustic complaint after echo. A cassette unit directly over the table blows cold air onto heads and adds fan noise exactly where the microphones are. Ducted supply through linear diffusers along the ceiling edge, at low air velocity, with acoustically lined ducts and no shared duct runs between adjacent rooms, keeps the room near the NC 25–30 range. Return air should not be taken through an open ceiling void shared with the next room, because that void becomes a speaking tube.

Finishes and furniture

With the hidden systems in place, finishes become simpler. Carpet tiles or acoustic vinyl underfoot; a mineral-fibre or acoustic-tile ceiling with a gypsum border to carry lights and diffusers; fabric, felt or slatted wood panels on the rear wall and the solid side wall; frosted bands on glass partitions at 900–1500 mm and above for privacy without losing daylight; a matte, light-coloured table top that does not reflect downlights into the camera; chairs on castors with quiet glides. Table power and data should rise through a flush lid or a grommet in the centre zone, never as cables trailing to a wall socket. A credenza at the display wall or at the rear can house the AV rack, with ventilation and a lockable door.

Item (10-seat room, ≈ 271 sq ft)SpecificationIndicative cost (Oct 2026)
Partitions, doors and glassInsulated stud wall to slab, solid-core door with seals, double-glazed front₹2–4.5 lakh — verify locally
Ceiling and acoustic treatmentMineral-fibre grid, gypsum border, ≈ 8–12 m² wall panels₹1–2.5 lakh
FlooringCarpet tiles₹22,000–55,000 (₹80–200 per sq ft)
Lighting and controlsLinear and wall-wash fittings, dimming, scene keypad₹60,000–1.5 lakh
Electrical, data and floor boxDedicated circuit, UPS outlets, LAN points, conduits₹40,000–1 lakh
Air-conditioning distributionSeparate zone, lined ducts, linear diffusers (equipment extra)₹27,000–68,000 (₹100–250 per sq ft)
Furniture3000 × 1200 table, 10 chairs, credenza₹1.6–6 lakh
AV86 in display, camera, microphones, speakers, presentation system₹6–15 lakh
TOTALComplete room≈ ₹12–32 lakh

Where conference rooms are heading

The direction is clear in new offices: fewer large boardrooms and many more small rooms — huddle rooms for two to six people and phone booths for one — because most meetings are small and many are partly remote. Equipment is converging on a few standard platforms that start a call with one touch, and cameras increasingly frame speakers automatically. Rooms are being designed for equity between people in the room and people on the screen: the display at eye level, the camera at the display, sound pick-up even across the table, and a front-of-room layout rather than a long boardroom table with remote faces at one end. Energy codes such as ECBC and green ratings from IGBC and GRIHA push for daylight, occupancy-based lighting and demand-controlled ventilation, which suit meeting rooms well because they are empty for much of the day. The fundamentals will outlast every gadget: a quiet, well-proportioned, well-lit room with good air.

Rules for designing a conference room

  • Size the room from the table: 750 mm per seat, 1000–1200 mm table width, 1200 mm or more clear behind every chair.
  • Size the display from the farthest seat: image height at least one-sixth of the distance for general content, one-quarter for detailed content.
  • Put the camera at the display, centred, close to seated eye level, and leave the seat nearest the screen empty.
  • Take every partition to the structural slab, seal head, base and sockets, and use solid-core doors with seals.
  • Treat the ceiling, floor and at least two facing walls with absorption to bring reverberation down to about 0.4–0.6 s.
  • Light faces from the front with diffuse sources, avoid downlights over heads, and control windows with blinds.
  • Give the room its own air-conditioning zone, fresh air by occupancy, and low-velocity supply away from the table.
  • Run conduits with draw wires from a table floor box to the rack, display and ceiling before anything is closed.

Frequently asked questions

What is the standard size of a conference room for 10 people?

About 6000 × 4200 mm (roughly 20 × 14 ft, 25 m²) with a 3000 × 1200 mm table. That gives 750 mm per seat, about 1500 mm behind chairs and 1800 mm between the display wall and the table. Smaller rooms work for occasional use, but circulation behind chairs suffers first.

What size TV or display is needed for a conference room?

Divide the distance to the farthest seat by six to get the minimum image height for general content, or by four for detailed content, then choose the screen whose height matches. For a 16:9 display the image height is about half the diagonal: a 75 in display suits roughly 5.6 m for general use, an 86 in about 6.4 m.

How can echo in a meeting room be reduced?

Add absorption: carpet or acoustic flooring, an acoustic ceiling over most of the room and fabric or felt panels on at least two facing walls at seated height. Curtains on glass walls help further. Aim for a reverberation time of about 0.4–0.6 seconds; most untreated rooms with tile floors, gypsum ceilings and glass are well above 1 second.

Why can people outside hear the conference room?

Usually because the partition stops at the false ceiling, the door has gaps, sockets are back-to-back or a duct connects the two spaces. Taking the partition to the slab with insulation and sealant, fitting a solid-core door with seals, staggering sockets and lining ducts typically solves it. Fabric panels inside the room do not.

What lighting is best for video conferencing?

Diffuse, neutral-white light from the front and sides of participants, around 3500–4000 K with good colour rendering, about 500 lux on the table and soft light on faces. Avoid downlights directly overhead and bright windows behind people facing the camera, and dim the light falling on the display.

Sources & standards

  1. Bureau of Indian Standards — IS 3646 (Part 1):1992, Code of practice for interior illumination: recommended illuminance for offices and meeting rooms
  2. National Building Code of India 2016, Part 8 (Building Services): lighting and ventilation, air-conditioning and acoustics, sound insulation and noise control
  3. ASHRAE Standard 62.1 — Ventilation for Acceptable Indoor Air Quality: outdoor air rates for conference and meeting rooms
  4. AVIXA — Display Image Size for 2D Content in Audiovisual Systems (DISCAS) standard
  5. ISO 717-1 — Rating of sound insulation in buildings and of building elements: airborne sound insulation (Rw)
  6. Bureau of Energy Efficiency — Energy Conservation Building Code (ECBC): lighting power and controls for offices
  7. Time-Saver Standards for Interior Design and Space Planning — conference seating and clearances
  8. Price ranges: indicative October 2026 estimates — confirm locally before budgeting
Discuss your project

Keep Reading

Related articles

All articles →
Banquet Hall Interior Design — cover
Commercial & Hospitality

Banquet Hall Interior Design

Plan a banquet hall at about 1.2–1.5 m² per guest for round-table dining (about 0.7–0.9 m² for theatre seating), with a clear height of 4.5–6 m, a stage 600–900 mm high and 4–6 m deep, and at least two remote, unobstructed exits sized by a fire consultant. Indicatively, interiors cost about ₹1,500–6,000+ per sq ft from basic to premium, before HVAC, kitchen equipment and GST.

Food Court Design — cover
Commercial & Hospitality

Food Court Design

A food court works when counters, seating and service are planned as one system: counters of about 200–600 sq ft with 4.5–7.5 m frontage and a 1.5–3 m queue zone, shared seating at about 1.1–1.4 m² per seat with 1200 mm main aisles, a tray-return and wash-up point, and a back-of-house corridor for goods and waste. Exhaust, gas and fire systems must be designed by qualified engineers under NBC 2016 and the landlord's rules.

Rooftop Restaurant Design — cover
Commercial & Hospitality

Rooftop Restaurant Design: Structure, Safety, Layout and Cost

A rooftop restaurant is a normal restaurant placed on the most difficult floor of a building: the roof must be checked for a dining load roughly two to three times what a terrace is usually designed for, waterproofed before anything is built on it, given two safe exits and a fire NOC, and edged with railings of 1100–1200 mm. Interior fit-out still runs about ₹900–3,500+ per sq ft, but rooftop extras for structure, waterproofing, railings and shade often add ₹300–900 per sq ft on top.